冷库蒸发式冷凝器的安装
2017-5-12 14:35:16
冷库蒸发式冷凝器一般安装在机房顶部,机房的屋顶结构需特殊处理,要求能承受蒸发式冷凝器的重量。
The freezer evaporative condenser is installed on the top of the machine room, the roof structure of the machine room needs special treatment, the weight of evaporative condenser is required.
冷库蒸发式冷凝器安装必须牢固可靠且通风良好,安装时其顶部应高出邻近建筑物300mm,或至少不低于邻近建筑物的高度,以免排出的热湿空气沿墙面回流至进风口;若不能满足上述要求时,安装时应在蒸发式冷凝器顶部出风口上装设渐缩口风筒,以提高出口风速和排气高度,减少回流。
Refrigerator evaporative condenser installation must be solid and reliable and well ventilated, the top 300 mm should be higher than that of adjacent buildings when installation, or at least not less than the height of the adjacent buildings, in order to avoid the discharge of hot wet air along the wall back to the inlet; If can not meet the above requirements, when installation should be on the top of the evaporative condenser outlet installed on reducing ram, in order to improve the export wind speed and height of exhaust, reduce reflux.
冷库蒸发式冷凝器的安装也有单台式和多台并列式等安装形式。安装时需注意与邻近建筑物的间距,一般要注意以下情况:
The installation of evaporative condenser in cold storage is also equipped with a single table and multiple side-by-side installations. When installing, pay attention to the space between adjacent buildings.
1.当蒸发式冷凝器四面都是墙时,安装时进风口侧的最小间距应为1800mm,非进风口侧的最小间距为900mm。
When the evaporative condenser is on all sides of the wall, the minimum distance between the inlet and the inlet side should be 1800mm, the minimum spacing of the non-inlet side is 900mm.
2.当蒸发式冷凝器处于三面是实墙,_面是空花墙时,进风口侧的最小间距应为900mm,非进风口侧的最小间距为600mm。
When the evaporative condenser is on three sides of solid wall, _ face is an empty wall, the minimum distance between the inlet side should be 900mm, and the minimum spacing of the non-inlet side is 600mm.
3.当两台蒸发式冷凝器并联安装时,如两者都是进风口侧,它们之间的最小间距应为800mm;如—台为进风口侧,另一台为非进风口侧时,其最小间距为900mm;如两台都不是进风口侧时,最小间距为600mm。
When two evaporative condenser is installed in parallel, the minimum distance between them should be 800mm. The minimum spacing is 900mm for the inlet side and the other side of the air outlet. If two are not in the inlet side, the minimum spacing is 600mm.
当蒸发式冷凝器采用同轴连接的离心式风机或水盘内设有电加热器时,上述2、3两种情况下,其最小间距应当加大,以利维修。
When evaporative condenser using coaxial connection centrifugal fan or water when the disc is equipped with electric heater, the above two cases, 2, 3, the minimum distance should be increased, and maintenance.
在保证蒸发式冷凝器与邻近建筑物之间的距离后,在安装时还要注意蒸发式冷凝器的水盘离地不宜小于500mm,以便于管道连接、水盘检漏和防止地面脏物被风机吸入。
In guarantee the evaporative condenser and the distance between the adjacent buildings, also notice when installation of evaporative condenser water dish should not be less than 500 mm from the ground, so that the pipe connection, water leak detection and prevent the dirt on the suction fan.
在进行冷库蒸发式冷凝器的配套安装时,对于单组冷却排管的蒸发式冷凝器与贮液器的进液配管,可用液体管本身进行均压,水平管段的坡度为1/50,坡向贮液器。如阀门安装位置受施工条件所限,可装在主管上,但必须装在出液口200mm以下。具体管道连接部分可参见第九节中关于蒸发式冷凝器管道连接方式等内容。
In the cold storage installation of form a complete set of evaporative condenser, cooling exhaust pipe for a single set of evaporative condenser and receiver into the fluid pipe, tube itself available liquid pressure, horizontal section of the slope at 1/50, slope to the receiver. If the valve installation position is limited to the construction conditions, it may be installed in the supervisor, but it must be installed below 200mm. The link section of the pipe can be seen in section 9 on the connection of the evaporative condenser pipe.